An accurate approach for the evaluation of the performance of overhead distribution lines due to indirect lightning

01 Pubblicazione su rivista
Andreotti A., Araneo R., Mahmood F., Pierno A.
ISSN: 0378-7796

The probability of flashovers due to indirect lightning on overhead lines is us ually calculated assuming a statistical distribution for the induced voltages, and a deterministic and specified value for the insulation level of the line. However, more accurate practices of insulation coordination suggest a statistical treatment for the insulation level too, in order to relate the probabilistic nature of both electrical stress (induced voltage) and the electrical strength (insulation level). In this paper, a statistical insulation coordination method is applied for the assessment of induced-voltage flashovers and, more in general, for the indirect lightning performance of the line. Such a statistical approach, which is inherently more accurate than the traditional approach, allows also to discriminate among probability of occurrence of flashovers on one, two, or on all phases.