Numerical analysis of mutual transient voltages in grounding systems of offshore wind farms

04 Pubblicazione in atti di convegno
Araneo R., Lovat G., Celozzi S., Burghignoli P.

The paper illustrates a numerical procedure for the computation of mutual transient overvoltages transferred among typical grounding systems of wind turbines belonging to the same wind farm. We use a hybrid approach based on circuit theory and Method of Moments in the frequency domain. The transient response is obtained by means of the Inverse Fourier Transform efficiently computed trough a double-exponential formula.