Intrinsically Safe Grounding Systems and Global Grounding Systems

01 Pubblicazione su rivista
Parise Giuseppe, Parise Luigi, Martirano Luigi
ISSN: 0093-9994

This paper introduces a characterization of grounding systems (GSs) and defines their condition of “conventionally safe” and “intrinsically safe.” A single GS and a set of GSs are intrinsically safe if they guarantee touch/step voltages permanently permissible for an assigned ground fault value. A new definition of global grounding systems (GGSs) is proposed, revising that offered by the Standards IEC 61936-1/EN 50522. A safety criterion, useful for urban and industrial areas with reduced accessibility, allows identifying the safety zone of influence, and the intrinsically safe condition of a single GS and of a GGS, constituted by a set of interconnected single GSs.

© Università degli Studi di Roma "La Sapienza" - Piazzale Aldo Moro 5, 00185 Roma