DEMO WCLL BB breeding zone cooling system design: analysis and discussion
The Water-Cooled Lithium-Lead (WCLL) Breeding Blanket (BB) is a key component in charge of ensuring Tritium self-sufficiency, shielding the Vacuum Vessel and removing the heat generated in the tokamak plasma. The last function is fulfilled by the First Wall (FW) and Breeding Zone (BZ) independent cooling systems. Several layouts of BZ coolant system have been investigated in the last years in order to identify a configuration that guarantee Eurofer temperature below the limit (823 K) and good thermal-hydraulic performances (i.e. water outlet temperature 601 K).